Cookies are important to the proper functioning of a site and we use them to help us offer you the best online experience. By using our website and/or clicking OK, you are agreeing to our use of cookies in accordance with our cookies policy. I Agree

FLIR FH-Series R PTZ Radiometric Thermal Camera

Tax included. Shipping calculated at checkout.

Please CONTACT US if you are interested in this product.



The FLIR FH-Series R PTZ combines radiometric thermal imaging, visible video and continuous pan-tilt coverage for early fire detection, surface-temperature monitoring and security. It helps operators find hot spots before ignition, verify alarms visually and monitor wide outdoor areas around the clock.

Request pricing and a site assessment


Detect heat early. Verify events fast.

  • MONITOR SURFACE TEMPERATURES

    Onboard radiometry measures minimum, maximum, average and differential temperatures across user-defined spots, boxes and polygon areas.

  • COVER WIDE OUTDOOR AREAS

    Continuous 360° pan, programmable presets and thermal imaging support scheduled patrols of industrial yards, stockpiles, processing areas and critical infrastructure.

  • VERIFY AND COORDINATE RESPONSE

    Visible video with 30× optical zoom helps operators assess smoke, hot spots and intrusions, while NEXUS and ONVIF support integration with compatible security systems.


Eight thermal configurations

Choose 9 mm, 13 mm, 25 mm or 35 mm thermal optics, with 30 Hz and export-compatible 9 Hz configurations. GoThermal can match the lens and frame rate to your monitoring distance, coverage area and regulatory requirements.

Model Focal length Frame rate
FH-617 R PTU 35 mm 30 Hz
FH-644 R PTU 13 mm 30 Hz
FH-625 R PTU 25 mm 9 Hz
FH-669 R PTU 9 mm 30 Hz
FH-669 R PTU 9 mm 9 Hz
FH-644 R PTU 13 mm 9 Hz
FH-617 R PTU 35 mm 9 Hz
FH-625 R PTU 25 mm 30 Hz

Designed for high-consequence sites

The IP66 system is designed for demanding outdoor environments. Typical applications include early fire detection around mines, warehouses, manufacturing plants, waste and recycling facilities, energy sites and other areas where a developing hot spot can cause injury, asset loss or operational shutdown.

Technical specifications

Compliance & Certifications
Compliance and certifications FCC Part 15, Subpart B, Class A; UL Listed; RoHS; WEEE; ONVIF Profiles S, G and T; IEC 62368. Certifications for the complete camera plus PTU assembly are pending.
Cybersecurity IEEE 802.1X; TLS/HTTPS; user authentication; firewall access control; credential policy enforcement; digest authentication.
Environmental
IP rating IP66
Operating temperature −35 °C to 65 °C (−31 °F to 149 °F)
Storage temperature Camera: −55 °C to 85 °C; PTU: −40 °C to 70 °C
Humidity Camera: 0–95% relative humidity; PTU: <90% relative humidity
Vandal resistance IK10, except windows; camera only
Shock and vibration IEC 60068-2-27 and IEC 60068-2-64; camera only
General
Detector type Long-life, uncooled VOx microbolometer
Enclosure Camera: NEMA 4X; PTU: aluminium alloy
Input voltage 24 V AC (±10%) or 24 V DC (±10%)
Power consumption FH-Series R PTZ with PTU: ≤150 W
Weight 18.1 kg (41.4 lb)
Measurement & Analysis
Object temperature range High gain: 0 °C to 160 °C; low gain: 0 °C to 380 °C
Accuracy Below 100 °C: ±5 °C; below 150 °C: ±5%; above 150 °C: ±15%, measured at 25 °C ambient. Inaccuracy may increase at extreme temperatures.
Radiometric analysis Minimum, maximum, average and differential temperature measurement in user-defined spots, boxes and polygon-shaped areas.
Pan-Tilt Unit
Pan 360° continuous; 0.1°/s to approximately 55°/s
Tilt −75° to approximately 40°; 0.1°/s to approximately 25°/s
Presets 200 valid preset positions; ±0.1° accuracy
System Integration
Ethernet 100/1000 Mbps
Network APIs NEXUS SDK, NEXUS CGI, ONVIF Profiles S, G and T
Alarm I/O Two dry-contact inputs and two relay outputs, 1 A maximum at 24 V AC/30 V DC; normally open or normally closed, configurable
Streaming resolution Thermal: 640 × 512. Visible: 1920 × 1080, 1280 × 720 and 640 × 480.
Supported protocols IPv4, HTTP, HTTPS, UPnP, DNS, NTP, RTSP, TCP, UDP, ICMP, IGMP, DHCP, ARP and IEEE 802.1X
Thermal Camera
Array format 640 × 512
Pixel pitch 17 µm
Sensitivity <35 mK at 25 °C, f/1.0
Spectral range 7.5 µm to 13.5 µm
Frame rate NTSC: 5–30 fps; PAL: 5–25 fps
Image controls Automatic flat-field correction, Auto AGC, Digital Detail Enhancement, brightness and contrast
Visible Camera & Video
Visible stream Up to 1920 × 1080 with 30× optical zoom
Visible F-number f/1.6–f/4.4
Compression H.264, H.265 and MJPEG; four independent streams, two visible and two thermal

Documents and downloads

Technical documentation published by FLIR and distributed by GoThermal — Unit 9, No 4 Homestead Avenue, Bryanston, Johannesburg, South Africa — Tel +27 11 557 9200 — sales@GoThermal.co.za


Frequently asked questions

What does radiometric thermal imaging add?

Radiometry provides contactless surface-temperature measurements, not only a thermal picture. Alarm rules can be based on temperature thresholds and changes within configured regions.

Can it be used for both fire detection and security?

Yes. The system combines radiometric thermal monitoring with visible verification and PTZ coverage. The final design, alarm logic and integrations should be engineered for the specific site and risk.

Which lens and frame rate should I choose?

The correct choice depends on target size, monitoring distance, required scene width and export regulations. GoThermal can specify the configuration from a site plan and operating requirements.

Does it replace a certified fire-detection or suppression system?

No. It is an early-warning and monitoring component. It should be integrated into a professionally designed fire-risk strategy and does not replace required certified detection, alarm or suppression systems.


Get a Quote

Send us your site layout, monitoring distances, target temperature range and VMS requirements. GoThermal will help specify the appropriate FH-Series R PTZ configuration and integration approach.